FR & FRLS Electrical Wires and Cables

Design & Quality

Design of a cable is highly complex owing to the two components, the current carrying copper conductor and insulation to isolate the conductor from each other and as well as surroundings.These two form the core of the cable. The copper and the PVC of TARUN FR PVC Wires and Cables meet high quality standards. TARUN FR PVC Wires and Cables are ISI marked and confirm to IS 694:1990 standard.

Nominal Area of  Conductor Number/ Nom.Dia of wire Thickness of insulation Approx. Overall Diameter Current Carrying Capacity
2 Cables single phase
Resistance(Max) Per Km @200C
Sq mm mm mm mm In Conduit/Trunking Amps. Unenclosed-clipped directly to a surface or on cable tray Amps. Ohms
0.75 11/.3* 0.7 2.5 7 8 26.0
1.00 14/ .3* 0.7 2.8 11 12 18.10
1.50 22/ .3* 0.7 3.2 14 16 12.10
2.50 36/ .3* 0.8 3.8 19 22 7.41
4.00 56/ .3* 0.8 4.4 26 29 4.95
6.00 84/ .3* 0.8 5.0 31 37 3.30
  • Electrolytic Grade copper having 99.96% purity & maximum conductivity to ensure minimum power losses & maximum safety.
  • Uniformly bunched copper wires of uniform diameter that makes stripping & crimping of wires easier & minimizes losses.
  • Indigenously developed PVC compound formulated from fines ingredients is produced in-house. High thermal stability & insulation resistance makes it suitable for use in Indian environment.
  • Double insulation,with primary insulation from virgin PVC & the Secondary insulation from high tensile vergin PVC ensures the strength of the cables.
Nominal Area of the Conductor

Sq. mm
Number / Nom Dia.of wire

(mm)
Insulation Thickness Nominal

(mm)
Approx. Overall Dia

(mm)
Current Carrying as per IS : 3961

(Amps.)
Max. Resistance at 20 C

Ohm/Km
10.0 80/.4 1.0 6.4 42 1.91
16.0 126./4 1.0 8.0 57 1.21
25.0 197./.4 1.2 10.0 71 0.780
35.0 276/.4 1.2 11.2 91 0.554
50.0 396/.4 1.4 13.0 120 0.386
70.0 360/.5 1.4 15.0 160 0.272
95.0 475/.5 1.6 18.0 200 0.206
120.0 608/.5 1.6 19.5 225 0.161

Product Images

1
6
3
5
4
2